Discovery Marine Manual Call Point – Outdoor 58200-975MAR

Description

58200-975MAR

The Discovery Manual Call Point is used to manually initiate an alarm signal on the fire detection system.

  • Suitable for weatherproof applications
  • EN 54-11 Certified
  • Resettable operating element
  • 170° viewable LED
  • XP95 & Discovery compatible
  • Not available for the UK market

Additional Information

General
Warranty  :  3 year
Mechanical
Colour  :  Red
Weight  :  325g
Materials housing  :  Polycarbonate
Product length  :  110mm
Product width  :  110mm
Product depth  :  74mm
Key type  :  Apollo Manal Call Point reset key
Product length  :  4.33in
Product width  :  4.33in
Product depth  :  2.91in
Conformance
Approvals
LR

CPR

MED

Electrical
Protocol voltage (max)  :  9V
Protocol voltage (min)  :  5V
Protocol voltage  :  5 to 9V peak to peak
Power-up surge current  :  1mA
Maximum power-up time  :  1 second
Quiescent current  :  100μA
Quiescent current tested at  :  24V dc
Environmental
Humidity (max)  : 95% RH
Humidity (min)  :  0% RH
Operating temperature (min)  :  -30°C
Operating temperature (max)  :  70°C
Operating temperature  :  -30 to 70°C
IP rating Value  :  IP67
Operating temperature  :  -22 to 158°F
Operating temperature (max)  :  158°F
Operating temperature (min)  :  -22°F