Intelligent Manual Call Point SA5900-908APO

Description

SA5900-908APO

The Manual Call Point is used to manually initiate an alarm signal on the fire detection system.

  • EN 54-11 & EN 54-17 Certified
  • Resettable operating element
  • 170° viewable LED
  • Suitable for semi flush or surface mounting
  • ‘Plug and Play’ terminal connections for faster wiring
  • Continuity link for wiring test before commissioning
  • XP95, Discovery and CoreProtocol compatible
  • Built-in Isolator

Additional Information

General
Warranty  :  10 year
Mechanical
Colour  :  Red
Weight  :  180g
Materials housing  :  Polycarbonate
Product length  :  90mm
Product width  :  90mm
Product depth  :  63mm
Key type  :  Apollo Manal Call Point reset key
Product length  :  3.54in
Product width  :  3.54in
Product depth  :  2.48in
Conformance
Standards  :  EN 54-11
             EN 54-17
Approvals
SBSC

VdS

FG

LPCB

BOSEC

CPR

Performance
Analogue value nominal  :  16
Alarm level analogue value  :  64
Fault level analogue value  :  4
Type  :  A
Operating element  :  Resettable element
Action  :  Single
Electrical
Protocol voltage (max)  :  13V
Protocol voltage (min)  :  5V
Protocol voltage  :  5 to 13V peak to peak
Power-up surge current  :  1mA
Maximum power-up time  :  1 second
Status indicator – Alarm  :  Red
Status indicator – Fault  :  Yellow
Status indicator – Isolate  :  Yellow
Status indicator – Poll  :  Flashing green
Quiescent current  :  100μA
Quiescent current tested at  : 24V dc
Supply voltage (max)  :  35V dc
Supply voltage (min)  :  17V dc
Supply voltage (Vmin-Vmax)  :  17 to 35V dc
Polarity  :  L1 & L2 are polarity sensitive
Environmental
Humidity (max)  : 95% RH
Humidity (min)  :  0% RH
Humidity  :  0% to 95% (no condensation or icing)
Humidity Note  :  no condensation or icing
Operating temperature (min)  :  -40°C
Operating temperature (max)  :  70°C
Operating temperature  :  -40 to 70°C
IP rating Value  :  IP44
Operating temperature  :  -40 to 158°F
Operating temperature (max)  :  158°F
Operating temperature (min)  :  -40°F